What this calculator does

A beam can be strong enough in bending yet still feel “bouncy” or crack plaster if it deflects too far. This tool uses the classic simply-supported uniform load formula δ = 5wL⁴ / (384EI) with E = 210,000 N/mm² and typical section second moments of area to give a planning estimate of mid-span deflection.

How to use it

  1. Choose the section — each option includes an approximate Iₓ value.
  2. Enter clear span — distance between supports in metres.
  3. Enter uniform load — line load in kN/m (floor/roof load + self-weight if needed).
  4. Pick a limit — L/360 for many domestic floors, L/250 for general beams.

Worked example

A 203×133×25 over a 4.0 m span with 12 kN/m UDL typically shows several millimetres of mid-span deflection. Compare that with L/360 ≈ 11.1 mm. If the estimate is close to the limit, discuss a deeper section or reduced span with your engineer — online tools are only a first pass.

Disclaimer: Simplified estimate only. Point loads, cantilevers, partial fixity, shear deflection and lateral-torsional buckling are not modelled. Building Control requires engineer calculations for structural work.

RSJ Deflection Calculator

Estimate mid-span deflection for a simply supported RSJ under uniform load and compare it with common UK serviceability limits (L/360 or L/250).

Include floor/roof load line + beam self-weight if needed

Deflection vs strength

Always check both. Use the load capacity calculator for a rough strength/utilisation view, and this page for serviceability. Then read our deflection guide for formulas and limits in more detail.

Need a starting section size first? Try the beam size calculator.

Frequently Asked Questions

What is an acceptable RSJ deflection?

Many domestic floor beams are checked against roughly span/360 under imposed load combinations. Your engineer will confirm the exact limit for your project and finishes.

Why does deflection grow so fast with span?

Deflection under uniform load rises with span to the fourth power. Doubling span can increase sag dramatically unless you increase section stiffness (Iₓ).

Does this include point loads?

No. Concentrated loads, trimmer beams and cantilevers need different formulas. Ask your structural engineer for those cases.

Will Building Control accept this result?

No. Use it for planning conversations only. Submit engineer-stamped calculations for approval.